Correct installation of the Earth Lekage Relay and toroid should ensure trouble free operation, if this documents is followed.
• Always ensure the Earth conductor Does Not pass through the toroid. If it is unavoidable,
the Earth must be routed back through the toroid again and around, as shown in Fig:2 beside.
• As a rule, select a toroid that has an inside diameter which is twice that or greater than
the outsider diameter of the cables to be passed through.
• Ensure the cable is central in the toroid.
• Place the toroid on a straight, section of cable, not near a bend.
• Keep the cable and toroid from intense magnetic fields from nearby equipment.
• Do not pass individual through seperate toroids, as shown in Fig: 3